Skip to content

Example Combined heat and power

florian.stinner edited this page Jun 20, 2022 · 1 revision

Combined heat and power (CHP)

Image of a combined heat and power unit

Number category assignment specification BUDO
1-10 system combined heat and power - CHP
1 subsubsystem sensor volume flow SEN+VF
1 medium natural gas - GAS.NAT
1 signal type measured value volume flow MEA+VF
2 subsubsystem sensor volume flow SEN+VF
2 medium air fresh/outside AIR+ODA
2 signal type measured value volume flow MEA+VF
3 subsubsystem sensor temperature SEN+T
3 medium exhaust gas - GAS.EHA
3 medium 2nd specification before exhaust gas heat exchanger - BEF.GAS.HX
3 signal type measured value temperature MEA+T
4 subsubsystem sensor volume flow SEN+VF
4 medium exhaust gas - GAS.EHA
4 medium 2nd specification before exhaust gas heat exchanger - BEF.GAS.HX
4 signal type measured value volume flow MEA+VF
5 subsubsystem sensor temperature SEN+T
5 medium exhaust gas - GAS.EHA
5 medium 2nd specification after exhaust gas heat exchanger - AF.GAS.HX
5 signal type measured value temperature MEA+T
6 subsystem motor - MO
6 subsubsystem sensor torque SEN+TQ
6 signal type measured value torque MEA+TQ
7 subsystem generator - GEN
7 subsubsystem meter electrical MET+EL
7 (example 1) signal type measured value electrical energy MEA+EN.EL
7 (example 2) signal type measured value electrical power MEA+POW.EL
7 (more examples) see Energy monitoring: no 2 - - -
8 subsubsystem sensor temperature SEN+T
8 medium water heating water WS+H
8 medium 2nd specification before exhaust gas heat exchanger - BEF.GAS.HX
8 signal type measured value temperature MEA+T
9 subsubsystem sensor temperature SEN+T
9 medium water heating water WS+H
9 medium 2nd specification after exhaust gas heat exchanger - AF.GAS.HX
9 signal type measured value temperature MEA+T
10 subsubsystem sensor temperature SEN+T
10 medium water heating water WS+H
10 medium 2nd specification before heat exchanger - BEF.HX
10 signal type measured value temperature MEA+T
Clone this wiki locally